This website uses cookies primarily for visitor analytics. Certain pages will ask you to fill in contact details to receive additional information. On these pages you have the option of having the site log your details for future visits. Indicating you want the site to remember your details will place a cookie on your device. To view our full cookie policy, please click here. You can also view it at any time by going to our Contact Us page.

BROWSE PRODUCTS
 

Looking at Power Factor

The imperative in industry to cut energy costs and reduce green house gases is good news for suppliers of high efficiency motors. However, the projected efficiency gains from using EFF1 or 2 type machines will not be achieved if motor system and supply problems that existed before they were installed are not resolved. One of the most common of these is low power factor says Adrian Larmour of Deritend.

Motors operated with low power factors are expensive and inefficient. In the worst cases this can result in utility supply companies having to increase their generation and transmission capacity to handle the reactive power component caused by inductive loads. There is a price for this: in the UK, the threshold value for power factor is 0.85, below this figure industrial users are generally charged more by their suppliers. In view of this, and because low power factor also reduces the distribution capacity of an electrical system -
increasing current flow and causing voltage drops - companies need to be aware of the problem and the measures they need to take to overcome it.

Low power factor is caused by inductive loads such as transformers and electric motors, which are a major
portion of the power consumed in industrial complexes. Unlike resistive loads that create heat by consuming kilowatts, inductive loads require the current to create a magnetic field, and the magnetic field produces the desired output. The total or apparent power required by an inductive device is a composite of Real power, measured in kW, and Reactive power, caused by the magnetizing current required to operate the device, which is (measured in kilovars, kVAR. An increase in reactive power increases the amount of
apparent power (measured in kilovolt amps, kVA) in a distribution system, and this causes a decrease in power factor.

For two systems transmitting the same amount of real power, the system with the lower power factor will have higher circulating currents due to energy that returns to the source from energy storage in the load. These higher currents in a practical system may produce higher losses and reduce overall transmission efficiency. A lower power factor circuit will have a higher apparent power and higher losses for the same amount of real power transfer.

There are a number of measures that can be employed to improve power factor. First, users should minimise the operation of idling or lightly loaded motors. Second, operation of equipment above its rated voltage should be avoided. Third, capacitors should be installed in motor circuits to decrease the magnitude
of reactive power. Fourth and final, standard motors should be replaced as they wear out with energy-efficient motors. However, here it must be said that even with energy-efficient motors, power factor is significantly affected by variations in load. Consequently, motors must be operated near their rated
capacity to realise the benefits of a high power factor design.

The benefits of undertaking these measures are many - a much reduced utility bill for a start. Moreover, with a corrected power factor losses in the distribution system are largely overcome, providing increased capacity for other loads to be connected. The optimised power factor also means that excessive voltage drops, which can cause overheating and premature failure of motors, are avoided leading to extended
equipment life. Finally there is the major environmental benefit: reduced power consumption means less CO2 emissions entering the atmosphere, helping to reduce the carbon footprint of industry generally.